Available models and kW options
Model names identify discrete variants. The heating and hot-water columns reproduce the stated output basis from the cited manufacturer documentation; they are not interchangeable. Where a model label differs from rated output, compare the rating rather than rounding it to the name. An oil model band describes that appliance’s settings, not every integer as a separate model to buy.
Condens 7000 WP: verified available variants and manufacturer output labels| Exact model / fuel variant | Fuel | Heating output (kW) | DHW output (kW) |
|---|
| Condens 7000 WP 50kW NG · Part 7 736 702 194 (base appliance; fuel configuration confirmed) | Gas (NG) | 46.5 Maximum nominal heat output at 80/60°C; 50/30°C maximum 49.9 kW | Not a combi DHW rating; cylinder design is separate |
| Condens 7000 WP 50kW LPG · Part 7 736 702 194 (base appliance; fuel configuration confirmed) | Gas (LPG) | 46.5 Maximum nominal heat output at 80/60°C; 50/30°C maximum 49.9 kW | Not a combi DHW rating; cylinder design is separate |
| Condens 7000 WP 65kW NG · Part 7 736 702 195 (base appliance; fuel configuration confirmed) | Gas (NG) | 62.6 Maximum nominal heat output at 80/60°C; 50/30°C maximum 69.5 kW | Not a combi DHW rating; cylinder design is separate |
| Condens 7000 WP 65kW LPG · Part 7 736 702 195 (base appliance; fuel configuration confirmed) | Gas (LPG) | 62.6 Maximum nominal heat output at 80/60°C; 50/30°C maximum 69.5 kW | Not a combi DHW rating; cylinder design is separate |
Domestic scope is verified by the dedicated 50/65 kW homeowner guide. The technical guide distinguishes 80/60°C and 50/30°C outputs; the homeowner product page uses different rounded labels. This catalogue excludes 85, 100, 125 and 145 kW commercial variants.
Unless an operating temperature is expressly stated, the current product-page output label does not specify its measurement temperature. The exact installation literature must be checked before technical design; no modulation range or seasonal performance claim is inferred here.